BidiTech · Advanced Water Process Control and Industrial AI
Contact Us
Precision Aeration Control
Home / Solutions / Precision Aeration Control

Precision Aeration Control

Built on predictive control of dissolved oxygen and ammonia nitrogen, airflow is allocated according to demand. Suitable for aeration systems in new wastewater treatment plants and in plants being upgraded to stricter discharge standards.

Overview

Aeration is one of the largest energy consumers in a wastewater treatment plant

Influent load varies significantly over the day, while conventional dissolved oxygen control mostly uses fixed setpoints and PID: at low load aeration is excessive, and at high load ammonia nitrogen may exceed limits.

Based on influent load and predicted effluent ammonia nitrogen, the BidiTech precision aeration system dynamically adjusts dissolved oxygen setpoints for each aeration lane and coordinates blowers and branch valves so that air supply matches actual oxygen demand.

Precision Aeration Control
Suitable for common biological processes such as A²O, AO, oxidation ditch and SBR
Key Technical Features

Control Structure and Technical Parameters

ItemDescription
Controlled VariablesDissolved oxygen (DO) in each lane, effluent ammonia nitrogen
Manipulated VariablesBlower airflow or discharge pressure, branch control valve positions
Feedforward and DisturbancesInfluent flow, influent ammonia nitrogen and COD, water temperature
ConstraintsMinimum dissolved oxygen, valve position range, blower operating range, effluent discharge limits
Operating ModesOpen-loop advisory / closed-loop control; can revert to the original control mode at any time
FAQ

Tendering and Implementation FAQ

For a technical proposal for a specific project, please contact the BidiTech technical team.

Do existing PLCs or blowers need to be replaced?

No. The system is implemented on top of the existing control system. The edge controller sends airflow or dissolved oxygen setpoints to the PLC, and existing equipment control and safety interlocks remain unchanged.

Which online instruments are required?

Typically dissolved oxygen analyzers in each biological tank, an online effluent ammonia nitrogen analyzer and airflow meters; influent flow, influent ammonia nitrogen and COD can be used as feedforward signals. Instrumentation is assessed before the project starts, and any missing instruments are listed in the proposal.

How is operational safety ensured?

Setpoints have upper and lower limits and rate-of-change limits. On abnormal instrument data, communication loss or manual switchover, the system automatically returns to the original control mode.

How is acceptance assessed?

Mainly on effluent compliance over an agreed period and energy consumption per unit of treated water, compared with pre-upgrade data under the same conditions. The specific criteria are defined in the contract.

Can it be implemented together with precision chemical dosing?

Yes. Aeration interacts with carbon source and phosphorus removal chemical dosing; they can be handled together in the same controller or implemented in phases.

Documentation